ad-100000402

Re-number the footnotes so they become the following:? CO2 monitoring is required in densely occupied spaces, in addition tooutdoor air intake flow measurement.? Project teams wishing to use ASHRAE approved addenda for thepurposes of this credit may do so at their discretion. Addenda must beapplied consistently across all LEED credits.

ad-100000400

Update the footnote references in the section so the text becomes the following:Monitor CO2 concentrations within all densely occupied spaces (those witha design occupant density of 25 people or more per 1,000 square feet).CO2 monitors must be between 3 and 6 feet above the floor.?Provide a direct outdoor airflow measurement device capable of measuringthe minimum outdoor air intake flow with an accuracy of plus or minus 15%of the design minimum outdoor air rate, as defined by ASHRAE 62.1-2007(with errata but without addenda?) for mechanical ventilation systemswhere 20% or more of the design

ad-100000404

In the first paragraph, remove the text "Design natural ventilation systems for occupied spaces to meet the recommendations set forth in the Carbon Trust "Good Practice Guide 237" (1998)."