Dear Sir/ Madam, I have a project that is a hotel with 200 guest rooms that are non-densely occupied. Each guest room floor (20 rooms per floor) is supplied with 3 AHUs. Therefore 100% of the OA suppled by these AHU are served in to the non-densely occupied spaces. However if I calculate based on the total OA requirement of the building there is no single guest room that takes 20% or more OA from that total OA requirement, but add up 200 guest rooms and then altogether they take more than 20% OA. Based on that I have the following questions. IEQc1 requires direct air flow measurement devices mechanical ventilation systems where 20% or more of the design supply airflow serves non-densely occupied spaces. But I'm not sure whether I should define "space" as a single guest room unit or all guest rooms together (because one AHU supplies air to multiple guest rooms). Secondly I'm also not sure whether 20% OA requirement is based on the total OA requirement of the building or the outdoor air supplied by each AHU. I appreciate clarification on this. Thank you very much.
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Add new comment
To post a comment, you need to register for a LEEDuser Basic membership (free) or login to your existing profile.