I am currently trying to get a lighting design to comply with SS Credit 1 Option 2 Path 6 and have a question. To get this credit there is a stipulation that the "After-hours override maybe provided by a manual or occupant-sensing device provided the override lasts no more than 30 minutes"

If i have a light fixture that falls under this credit and it is controlled by a occupancy sensor that turns on the lights after hours when someone eneters the room and then shuts off the lights 30 minutes after the occupant leaves I think would meet the credit criteria. However, a co-worker is trying to tell me that the light has to shut off after 30 minutes regardless if some one is in the room or not. So if it is after hours and a person enters the room the lights will go on but after 30 minutes they shut off ever if the person is still in there.

My Co-workers interpretation doesn't make a whole a lot of sense to me, has some one gotten this credit and can help me set my co-worker, or me, straight.

Thanks

Ben