Confirm that all chemical storage areas, high-volume copy rooms, etc. have:
deck-to-deck partition walls or hard-lid ceilings;
self-closing doors;
designated exhaust (no recirculation); and
an exhaust rate of 0.5 CFM/SF, with a pressure differential in relation to surrounding spaces of at least 5 Pa (0.02 inches on water gauge), on average or, when doors are closed, 1 Pa (0.004 inches on water gauge), at a minimum.
Design in space for additional ductwork that might be needed to provide designated exhaust for all garages, high-volume copy rooms, janitors’ closets, science labs, workshops, art rooms, or any other spaces that may be used for mixing and storage of chemicals or hazardous materials.
Design an adequate space for ten-foot entryway systems at all regularly accessed building entries. Evaluate all other building entrances—such as employee and service doors—for regular use, which may require entryway systems or roll-out mats.