All occupied spaces in naturally ventilated buildings require the installation of at least one CO2 sensor. The number of CO2 sensors depends on the project’s design and should be calculated by the mechanical engineer. Projects can use one CO2 sensor

All occupied spaces in naturally ventilated buildings require the installation of at least one CO2 sensor. The number of CO2 sensors depends on the project’s design and should be calculated by the mechanical engineer. Projects can use one CO2 sensor for multiple spaces only if the project is ventilated by an approved “engineered natural ventilation system” according to ASHRAE 62.1-2007 requirements and if it does not require occupant intervention.

All monitoring devices must be able to trigger an alarm or automated response when actual measurements vary by 10% or more in either direction from the design set points. The signal or alarm is most often relayed to a building management system that balan

All monitoring devices must be able to trigger an alarm or automated response when actual measurements vary by 10% or more in either direction from the design set points. The signal or alarm is most often relayed to a building management system that balances supply and return air volumes, monitors and controls minimum fresh air volumes, and provides a reliable reference point for commissioning of VAV systems. The alarm can be audible or visual and be relayed to building facility staff or directly to the occupants, to alert them to open windows.

The mechanical engineer and architect identify densely and non-densely occupied spaces as defined by LEED and determine the quantity and locations of all monitoring devices, and integrate them into the HVAC system. The mechanical engineer should verify th

The mechanical engineer and architect identify densely and non-densely occupied spaces as defined by LEED and determine the quantity and locations of all monitoring devices, and integrate them into the HVAC system. The mechanical engineer should verify that the monitors are designed to interface with a BMS system or trigger an audible or visual alarm if CO2 concentrations or ventilation rates fall outside of the required range.