100002317 Renewable Energy EP

Add an exemplary performance section:

"Exemplary Performance

For each Tier, procure renewable energy to meet or exceed the percentage of site energy specified in the final row, labeled "EP", of Table 1. Points for Renewable Energy Procurement. Projects can earn up to 1 point for meeting any of the Exemplary Performance thresholds shown in Table 1."

100002329 Site Development GFA

Edit the title and first sentence of Step 6 to read as follows:

Step 6. Determine Anticipated Ratio of Building Gross Floor Area (GFA) to Previously Disturbed Site Area
Determine the density of the project and surrounding areas by estimating the projected size of the building gross floor area (GFA) and comparing it with the site area.

100002330 v4 Data centers ASHRAE model guidance correction

Under the heading "ASHRAE model with full IT loading (model 3)", delete the following sentence:

"For the baseline models, the air temperature at the inlet of the server should be within ASHRAE’s recommended values, from 80.6°F (27°C) dry bulb and 59.0 °F (15°C) dew point to 64.4°F (18°C) dry bulb and 41.9°F (5.5°C) dew point, unless justification can be provided for an alternative minimum supply air temperature at the server inlet."

ad-100000349

At the end of the first paragraph, add the text "Any area that is being improved upon (for example site area that is being restored to its natural state) must be included in the landscape area."

ad-100000347

Replace the second sentence with "However, if such areas are included, they must be included in all other applicable Water Efficiency credit calculations (unless otherwise noted)."