Hi All,
I want to get a clarity on what shall I consider as my total building cooling tonnage while doing the base case energy model using eQuest. The eQuest generated LS-C report which gives the building peak cooling load excluding the outside air ventilation load.
Now, in a recent project to check the impact of this outside air ventilation load I removed the entire fresh air supplied to the spaces. After doing this my HVAC summary was giving a total cooling load of around 2800 TR whereas the LS-C report was showing that the building peak cooling load was 5168 kW or 1476 TR only. This huge difference in the net cooling load generated from both these reports is what is generating this confusion on what to follow with a logical reasoning.
Therefore, I request your confirmation and explaination on which report to follow LS-C report or the HVAC summary generated in the air side summary tab of the software.
Thanks in advance.
From what I understand, LS-C report is generally a good representation of coincident building level peak, though it omits the ventilation load and any oversizing factor.
Since plant capacity is auto sized by default based on secondary loop load, which is summation of coils peak load (non-coincident peak, thus inflated number), it will always stay higher than LS-C even with zero ventilation. In your case, this difference is almost 100%, which doesn't sound right.
I would suggest to check if auto sizing applied at multiple levels (in system and in loop).
If auto sizing is correctly applied, I would suggest switching to Primary for loop sizing but then it requires iterations to manually input correct plant size until no unmet hours reported.