CI-v4 EAc2:Optimize energy performance

Need to clarify about energy simulation

Hi all, On one of our project having 8 floor that was occupied under only with fourth storey which has undergone with system 8 for Energy simulation. In this case, I need guidance on whether we should take into account all 8 floors or just the fourth story when simulating the energy use of the entire building.
0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Fri, 01/27/2023 - 19:03

You only need to model the tenant space. There is specific guidance for how to model the tenant space with central systems in the LEED Reference Guide.

Tue, 03/21/2023 - 19:47

Hi Marcus, I am looking through LEED ID+C V4 reference guide and I am not able find the guidelines on how should I model my proposed HVAC system as well as Baseline, could you point me in the right direction?   Thanks!   Rajat Wadhwa

Wed, 03/22/2023 - 18:05

Look under the Further Explanation section. Do you have a hard copy or the online version? I always use the online version as it is always up-to-date. The proposed gets modeled as designed. If there are base building HVAC elements then see the section called - Contribution of Base Building HVAC and Service Water-Heating Systems. For the baseline see the section titled - Building the Baseline Energy Model. All of this is in the Minimum Energy Performance prerequisite, not the Optimize Energy Performance credit. 