Forum discussion

NC-v4.1 EAp2:Minimum Energy Performance

Ratio Windows/Wall in baseline model Table G1.1.1-1

Dear Srs, I hace a question about the ratio windows/walls in leed v4.1. Is for a building with two differents uses: 3.117 m2 of office and 13.472m2 of warehouse.

When we had modeled the windows of the proposed, we use the project details, perfect. The % of windows/walls  are 2% for warehouse and 32,4% for office. A 9,6% total for the proposed building.

This is our first project with the ashrae 90.1-2016, and we had read the TAble G3.1.5.d that adress you to the table Table G3.1.1-1 to use a ratio windows/walls different for each use. 

The Table marks 31% for office (465-4.650m2) and 6% for warehouse. I didn't found anyway that said you need to use the mininum of the two values (as the 2010 version). Then we use 31% and 6% for the baseline model, for a 12,3% fot whole baseline building.

I think this is a correct for the building with the ASHRAE 2016 version. with different % for the two buildings.

Now the LEED revision, ask us to use the minimum value beetween 40% ratio window/wall or the proposed value... as the 2010 version.

Which is the correct value for the LEED v4.1?

1

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 06/23/2021 - 18:38

It appears to me that you have correctly interpreted the baseline window area. If your reviewer has indicated that you should change the window area I would submit a project team inquiry to have the reviewer take another look. Make your case as above.

Wed, 05/31/2023 - 20:40

What was the response from the reviewer?