Forum discussion

Data-Centers-NC-v4 EAp2:Minimum energy performance

PUE calculation

Dear LEED user,

Someone could tell me, the value that i have to compare to the PUE of my project?
Do I have to calculate a PUE max? In this case, how can I calculate or find the PUE max?

Thank you in advance for your answers.
Marion

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 09/12/2019 - 17:45

The PUE is calculated for both the startup IT load and full load IT load energy models. The PUE values will be calculated automatically in the Performance Outputs tab of the v4 Minimum Energy Performance Calculator when the results are entered. Make sure you select LEED v4 BD+C: Data Centers as the rating system in the General Information tab. This is the only way the data center related calculations will show up in the Performance Outputs tab. The Data Centers Reference Guide includes the details for completing the startup IT load and full load IT load energy models.