Hi Marcus,
If the capacity is already out of range stated in ASHRAE 90.1-2010 Table 6.8.1D for Packaged Air-conditioning system SPVAC - (Cooling Mode) with maximum 240,000 BTU/h, can the project still use larger capacity as long as it meets the minimum 8.6 EER?
-Marie
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5907 thumbs up
December 11, 2018 - 9:51 am
Yes. Technically there is no minimum efficiency required since the standard does not address the equipment in question.