I’m modelling a System 8 baseline model according to ASHRAE 90.1-2010.

An exhaust energy recovery system is needed according to table 6.5.6.1.

Since the building is located in climate zone 4A (Milan, Italy) no economizer is requested.

Shall the heat exchanger have no control logics? No bypass?

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 06/20/2018 - 14:21

That's correct there are no controls or bypass.

Add new comment