Hi,
I have a question concerning requirements of section 5.4.3.4 of ASHRAE 90.1-2007.
The project consists of a new building (exstension) called “boarding areas” that is linked through a new tunnel named “CDC” (that is part of the new building) to the existing airport. The function of the building is to let people to move from airplanes to terminal and from terminal to airplanes. Only openings at +0.00 level towards are considered entrance to the building, so subject to requirements of section 5.4.3.4 of ASHRAE 90.1-2007 (double doors vestibule, equipped with self-closing devices, not necessarily operating at the same time for a walk through).
The other boundary openings are:
1. the beginning of connecting body, which connects the new building to the existing building (airport terminal);
2. fixed boarding bridge doors, which connect fixed boarding bridges to aircrafts through mobile boarding bridges;
Both (1+2) connecting the building to other conditioned space, so not are intended as entrance from outside.
Emergency exits are present at various building level, but are not intended to be used as building entrance.
Due to previous reasons, can boundary openings (point 1 and 2) may not to be subject to requirement of section 5.4.3.4 of ASHRAE 90.1-2007?
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5907 thumbs up
April 10, 2018 - 11:33 am
I agree. Makes sense to me.