NC-v4 EQp1:Minimum indoor air quality performance

Tab 6-1 and 6-4

Art classrooms are considered both in Tab. 6-1 and in Tab. 6-4. If we respect Tab. 6-4, could we avoid the verification of Tab. 6-1 (i.e. could we avoid the outdoor air supply)?

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 04/20/2017 - 15:37

Why you would want to do that? My reading of 62.1-2010 is that you must meet both requirements. And what goes out must be replaced somehow.