I need to ensure that in the 60/60 rule, I do not find anything about the maximum indoor temperature during flush-out, please advice if I can maintain any indoor temperature as long as it is above 60 F.
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Dave Hubka
Practice Leader - SustainabilityEUA
LEEDuser Expert
530 thumbs up
May 11, 2016 - 8:22 am
There is no maximum temperature limit for v3 projects. However v4 projects cannot exceed 80 F (27 C).
Omar Elrawy
Green Building Consultant | ResearcherGreenA Consultants
56 thumbs up
May 12, 2016 - 4:05 am
Thanks David. I need also to know the minimum acceptable measurement interval. Meaning that I will be preparing a log for CFM, Temp, Humidity, and commutative CF over time, and flush-out will take a total of 30 days, so; is it OK to take two readings per day for example?
Dave Hubka
Practice Leader - SustainabilityEUA
LEEDuser Expert
530 thumbs up
May 12, 2016 - 8:21 am
There is no required minimum measurement interval. However from Landry Watson's post below, GBCI asked for hourly readings during the flushout.
Two readings per day should suffice, if taken 12 hours apart and there are no significant outdoor temperature drops and no significant outdoor relative humidity increases.