FAQs about EAp2 :

Our project has a large process load—75%. Despite our efforts to make an efficient HVAC design, the cost savings are minimal. What can we do to earn this prerequisite and be eligible for LEED certification? Is there any flexibility in how we model the p

Can SHGC be higher in the proposed than in the baseline model?

Our process load is higher than 25%. Do we have to justify that?

Do I need to justify the electrical and fuel rates I am using in my model?

Our local code references ASHRAE 90.1-2010. Should I use that for my documentation, or 90.1-2007?

Can I claim exterior lighting savings for canopy lighting even though a baseline model cannot include shading elements?

The project is built on a site with existing exterior lighting installed. How should this be accounted for?

Can mezzanines open to floors below be excluded from the energy model?

How do I provide a zip code for an international location?

For a project outside the U.S., how do I determine the climate zone?

For a project outside the U.S., how do I determine the Target Finder score?

Do hotel rooms need automatic light shut-off control?

How commonly are the 90.1 mandatory compliance forms submitted as part of EAp2/EAc1?

The Section 9 space-by-space method does not include residential space types. What should I use?

Can the Passive House Planning Package (PHPP) be used to energy model for LEED?

Is it acceptable to model a split-type AC with inverter technology compressor as a heat pump, like modeling VRF?

Can the Trace 700 'LEED Energy Performance Summary Report' by uploaded to LEED Online in lieu of the Section 1.4 tables spreadsheet?

A portion of our building envelope is historic. Can we exclude it from our model?

Which baseline HVAC system do I use if my building has no heating or air conditioning?

For an existing building, do I need to rotate the model?

View answers »

Forum discussion

NC-2009 EAp2:Minimum Energy Performance

Water Chiller and relative Pumps-System 8

Dear All, I’m modelling a water centrifugal chiller in System 8 of ASHRAE 90.1 (Appendix G), using HAP by Carrier. I have to need how calculate the minimum entering condenser water temperature (ECWT) for a water-cooled chiller and the part-load ratio below which cycled operation occurs. This cycling point is defined as a percentage of full load capacity. How I could calculate these data? Should I consider 21 °C as minimum temperature? About Cooling Control I understand that 2 chiller equally sized have to be equally unloading. Am I right? No instructions are given for Cooling Tower: Full Load Fan kW, fan electrical Efficiency and % Airflow at Low fan Speed. Where can I get these data? Then I have to model the Primary/Secondary Systems with variable-speed. In my case the building has a floor area more than 20,000 m2. I have to put in the software the “Mechanical and Electrical efficiency” and the “W/L/s” for both pumps in Primary Loop and in Secondary Loop. How could I calculate the data for the two loops? The ASHRAE in the Section G3.1.3.10 gives me only 349 kW/1000 L/s but not the other data. Moreover I have to put in these data for the secondary loop: Control Head (kPa) and Minimum Pump Flow (%). Thanks.

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Mon, 03/16/2015 - 17:21

HAP will automatically calculate many of these variable once you select the basic system type. Sounds like you need some help from someone who knows HAP better than I. Contact HAP technical support or you could try the HAP Users group at onebuilding.org. The only item on your list that is defined by 90.1 is the cooling tower fan power which is 38.2 GPM/HP in my IP version from Table 6.8.1G. The new Section 1.4 spreadsheets may help you with modeling the Baseline systems.

Wed, 03/18/2015 - 07:58

Thank you so much for your suggestion. I'll follow that.