Hallo, we are trying to pursue Option 3
1.We are encountering difficulties finding a provider to test a window assembly under ASTM-331. Can we design an in-house test to be performed by the general contractor or does it have to be a certified provider?
2.Is there a minimum set of tests to be performed on the building envelope (blow door, air leakage...) or is it to the BECx Agent's discretion?
GH
Alicia Villanueva
CEORevitaliza consultores
76 thumbs up
February 3, 2014 - 1:59 pm
1. I mean we are finding difficulties in finding a provider to perform FIELD TESTS. Instead, we would like to do the tests by ourselves, following ASTM/AAMA standards. Is this acceptable?
Susan Walter
HDRLEEDuser Expert
1296 thumbs up
February 3, 2014 - 2:03 pm
Alicia - it is my understanding that the tests need to be overseen by a third party. This may be that you can do the physical work but not without the third party.
As for your second question, I belive that you need to test each condition if you are not doing a blower test. Blower tests aren't effective in large structures and not typically done in hospitals.
Susan