Return plenums should be used in the baseline model?

Hello, If in the proposed building there are plenums specified as return air path in the HVAC system, should I use them or ignore them in the baseline model? Thank you,

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 08/20/2013 - 14:40

You can ignore them as Appendix G does not specify the nature of the returns. Whether the returns are ducted or plenum only makes a difference in the baseline fan power calculations when applying that pressure drop adjustment (which you can't take if you don't have ducted returns in the design).