the project primary HVAC system is VRF+DOAS.
there is one work shop space that have no indoor VRF unit but outdoor air intake through DOAS.
DOAS is not intended for conditioning space. just for the comfortable occupancy.
in this case, what should I model baseline and proposed?
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5909 thumbs up
July 23, 2013 - 9:56 am
Always model the Proposed as designed/constructed.
For the Baseline select the system from Table G3.1.1A. Sounds like electric heat so enter the table under the electric column. Sounds like it is not residential, so you are a system 4, 6 or 8 depending on the size of the building.