FAQs about EAp2 :

The project is built on a site with existing exterior lighting installed. How should this be accounted for?

Can mezzanines open to floors below be excluded from the energy model?

How do I provide a zip code for an international location?

For a project outside the U.S., how do I determine the climate zone?

For a project outside the U.S., how do I determine the Target Finder score?

Do hotel rooms need automatic light shut-off control?

How commonly are the 90.1 mandatory compliance forms submitted as part of EAp2/EAc1?

The Section 9 space-by-space method does not include residential space types. What should I use?

Can the Passive House Planning Package (PHPP) be used to energy model for LEED?

Is it acceptable to model a split-type AC with inverter technology compressor as a heat pump, like modeling VRF?

Can the Trace 700 'LEED Energy Performance Summary Report' by uploaded to LEED Online in lieu of the Section 1.4 tables spreadsheet?

A portion of our building envelope is historic. Can we exclude it from our model?

Which baseline HVAC system do I use if my building has no heating or air conditioning?

For an existing building, do I need to rotate the model?

Our project has a diesel backup generator. Should we include it in our energy model?

Our project has a large process load—75%. Despite our efforts to make an efficient HVAC design, the cost savings are minimal. What can we do to earn this prerequisite and be eligible for LEED certification? Is there any flexibility in how we model the p

Can SHGC be higher in the proposed than in the baseline model?

Our process load is higher than 25%. Do we have to justify that?

Do I need to justify the electrical and fuel rates I am using in my model?

Our local code references ASHRAE 90.1-2010. Should I use that for my documentation, or 90.1-2007?

View answers »

Forum discussion

NC-2009 EAp2:Minimum Energy Performance

semi-heated spaces

What will be the effect on energy consumption if i model conditioned (warehouse) space as semi-heated space by using system type#9 or #10 in baseline. my dominant baseline system type is #5 (VAV)

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 01/17/2013 - 15:04

Too many variables to say for sure. Heating efficiency is about the same. Fans are constant vs VAV. No cooling energy. In general the consumption should be lower but possibly not in all cases and climates.

Thu, 01/17/2013 - 16:42

Your warehouse loads are likely more than 10 btu/sf different than the rest of the building, in which case you would have to use a secondary system (type 3 or 4) for that zone anyway. In this case, the primary benefit of this change would be modeling simplicity because you wouldn't have to fool with the DX component of systems 3 or 4.

Fri, 01/18/2013 - 07:12

thank you so much sir(s). If we model warehouse as conditioned space in baseline case (where as it is actually a semi-heated space : proposed), identical cooling should be model in the proposed which might be not much benefited. If we use system type 9 or 10 which doesn't require cooling thus no need to model cooling in proposed/baseline case , results in more savings.

Fri, 01/18/2013 - 17:05

The typical workaround for what you described is to simply set the thermostat high enough so the cooling never turns on in your baseline case.