In the proposed design, we are using a water-to-water heat pump for the sole purpose of service water heating. Voltage and Amps are 460v and 140 RLA, respectively. It is coupled with an unfired storage tank (Which Table 7.8 requires to have R-12.5 insulation). What water heater from Table 7.8 should I use in the Baseline model?
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5906 thumbs up
April 24, 2012 - 11:22 am
See Table G3.1-#11(Baseline) for the details on sizing, etc. Basically you will be modeling an electric storage type water heater in the Baseline sized according to Section 7.4.1.