leed credit EAc4

Having built a cafeteria at a local University we are having trouble getting the Q (tons ) for some of the refrigerated display equipment. Has anybody had luck getting this information for True Mfg. Models TSSU-48-12, TSSU-60-10, TPP 44, TAC 48, G4SM-23PT. We have contacted the MFG.s engineering dept and they have indicated they do not have this info. We do have the refrigerant charge on some of this equipment but need the tons to calc the total. Thanks any help greatly appreciated

1

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 04/17/2012 - 21:48

Hello and thank you for your inquiry. Please see the answers to your question below: MODEL / REFRIGERANT / COOLING RATINGS (BTUH) / HEAT OF REJECTION (BTUH) / TONS COOLING TSSU-48-12 / R134a / 2070 / 3105 / 0.26 TSSU-60-10 / R134A / 2070 / 3105 / 0.26 TPP-44 / R134A / 2070 / 3105 / 0.26 TAC-48 / R404A / 9350 / 14025 / 1.17 G4SM-23PT / R134A / 2601 / 3902 / 0.33 Please let me know if you have any other questions -Craig

Fri, 03/06/2015 - 06:29

Hi Craig, Thanks for the information. Will you also have the refrigerant mass and cooling capacity for the True Mfg. model T-24-GC-S? We got the refrigerant which is R404A but we are having difficulty getting the rest of the information we need to get the Rc. Thanks!