Problems with version 3 of the Form and Vot

RE: IEQp1 Form Table. Case 1: ASHRAE 62.1-2007 Ventilation Rate Procedure (LEED O&M v3) I fill out the table based on the critical zone for that AHU, but the Form(Version 3) automatically calclulates and enters Vot ( even though it doesnt have sufficient information )-- rather that letting me input Vot from the LEED calculator spreadsheet. Either I totally misunderstand the table, or it is goofy - anyone else having this issue ??

3

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 08/24/2011 - 11:13

Table "Case 1: ASHRAE 62.1-2007 Ventilation Rate Procedure" auto-calculates Rp, Ra, Vbz, Voz, and Vot. If you are are using a different calculation / spreadsheet to show compliance check the "The project team is using an alternative compliance approach in lieu of standard submittal paths" box under the ADDITIONAL DETAILS heading on the template.