Hi, I am about to model the baseline HVAC but it's not clear to me how i should select the energy source to determine the system according to table G3.1.1A of standard 90.1. The project is a renovation of an existing building, the proposed system (VRF) uses electricity as energy source while the existing system uses a fossil fuel boiler. Which is the criterion to select the baseline HVAC? Thanks
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
It is based on the installed system so enter the table under the electric column.
Hi Marcus,
I have a similar case but im struggling to find the base case COP for my project.
Building size is 8500m2.
Base case HVAC system is System 6 packaged VAV with PFP.
Proposed design is VRF system with EER of 11.2 (COP - 3.28)
Can you please help me determine the base case.
The owner of the project is aiming at minimum 21% savings for this project.
Thanks - Sriman
For a system 6 the cooling efficiency is taken from Table 6.8.1A. The cooling efficiency is dependent on the size of the system. The heating efficiency for electric resistance is 100% or a COP of 1.0.