I have York Chillers which are used very rarely and only under extreme hot weather conditions, requiring additional cooling.
Unfortunately these Chillers still use R-11 CFC Refrigerant. They also fall under the criteria of Conversion would not make it Economically Feasable to convert. Including all the supporting documentation for annual controlling leak rate of 5% or less.
Does this mean we get kicked to the curb on this one and thers no way we can qualify. Or is it automatically excepted considering it meets E.A. Preq.3 requirement guidelines for CFC based refrigerants.
Please advise - Rey
Chris Nixon
Manager, Sustainable SolutionsBRSC
36 thumbs up
April 30, 2010 - 8:00 am
I think you're kicked to the curb. I was going to suggest entering your numbers in the template and seeing if it were less than 100. However, when I tried it under an EBOM 2008 template, R-11 wasn't even a choice on the drop down menu. I suspect that you could still work the formula by hand (the template normally does it for you) but with R-11 your total will be more than 100.