Credit achievement rate
XX%
Upgrade to LEEDuser Premium to see how many projects achieved this credit. Try it free »
LEEDuser’s viewpoint
Frank advice from LEED experts
LEED is changing all the time, and every project is unique. Even seasoned professionals can miss a critical detail and lose a credit or even a prerequisite at the last minute. Our expert advice guides our LEEDuser Premium members and saves you valuable time.
Credit language
© Copyright U.S. Green Building Council, Inc. All rights reserved.
Requirements
Install permanent, continuous monitoring systems that provide feedback on ventilation system performance to ensure that ventilation systems maintain minimum outdoor airflow rates under all operating conditions.
AND
Case 1. Mechanical ventilation systems
Provide an outdoor airflow measurement device capable of measuring (and, if necessary, controlling) the minimum outdoor airflow rate at all expected system operating conditions within 15% of the design minimum outdoor air rate. Monitoring must be performed for at least 80% of the building’s total outdoor air intake flow serving occupied spaces. The outdoor airflow measurement device(s) must take measurements at the system level (i.e., the air-handling unit). The device must be monitored by a control system that is configured to trend outdoor airflow in intervals no longer than 15 minutes for a period of no less than 6 months. The control system must be configured to generate an alarm visible to the system operator if the minimum outdoor air rate falls more than 15% below the design minimum rate. All measurement devices must be calibrated within the manufacturer’s recommended interval.Case 2. Mechanical ventilation systems that predominantly serve densely occupied spaces1
Have a CO2 sensor or sampling location for each densely occupied space and compare it with outdoor ambient CO2 concentrations. Each sampling location must be between 3 and 6 feet above the floor. Test and calibrate CO2 sensors to have an accuracy of no less than 75 parts per million (ppm) or 5% of the reading, whichever is greater. Sensors must be tested and calibrated at least once every 5 years or per the manufacturer’s recommendation, whichever is shorter. Monitor CO2 sensors with a system configured to trend CO2 concentrations in intervals no longer than 30 minutes. The system must generate an alarm visible to the system operator and, if desired, to building occupants if the CO2 concentration in any zone rises more than 15% above that corresponding to the minimum outdoor air rate required by IEQ Prerequisite 1. CO2 sensors may be used for demand-controlled ventilation provided the control strategy complies with ASHRAE Standard 62.1-2007 ventilation rate procedure (see IEQ Prerequisite 1: Minimum Indoor Air Quality Performance, including maintaining the area-based component of the design ventilation rate).Case 3. Natural ventilation systems
Locate CO2 sensors in the breathing zone of every densely populated room and every natural ventilation zone. CO2 sensors must provide an audible or visual alarm to the occupants in the space and to the system operator if CO2 conditions are greater than 530 ppm above outdoor CO2 levels or 1,000 ppm absolute. The alarm signal must indicate that ventilation adjustments (e.g. opening windows) are required in the affected space. All monitoring devices must be calibrated within the manufacturer’s recommended interval. Permanently open areas must meet the requirements of ASHRAE 62.1-2007, Section 5.1 (with errata but without addenda2). Exemptions: If the total square footage of all space served by natural ventilation systems is less than 5% of total occupied square footage, the project is exempt from the requirements of this section. Rooms smaller than 150 square feet are also exempt. See all forum discussions about this credit »What does it cost?
Cost estimates for this credit
On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.
Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.
This information is also available in a full PDF download in The Cost of LEED v4 report.
Learn more about The Cost of LEED v4 »Frequently asked questions
See all forum discussions about this credit »Addenda
2. For densely occupied spaces, document compliance with Case 2.
3. For all AHUs, document compliance with Case 1. Use Table 2 to identify each AHU, the presence of appropriate monitoring for that unit, and the minimum required outdoor airflow for that unit (as generated via compliance with IEQ Prerequisite 1). Use Equation 2 to calculate the portion of the building’s total outdoor air intake flow serving occupied spaces."
Checklists
Step by step to LEED certification
LEEDuser’s checklists walk you through the key action steps you need to earn a credit, including how to avoid common pitfalls and save money.
Documentation toolkit
The motherlode of cheat sheets
LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.
Get the inside scoop
Our editors have written a detailed analysis of nearly every LEED credit, and LEEDuser premium members get full access. We’ll tell you whether the credit is easy to accomplish or better left alone, and we provide insider tips on how to document it successfully.
© Copyright U.S. Green Building Council, Inc. All rights reserved.
Requirements
Install permanent, continuous monitoring systems that provide feedback on ventilation system performance to ensure that ventilation systems maintain minimum outdoor airflow rates under all operating conditions.
AND
Case 1. Mechanical ventilation systems
Provide an outdoor airflow measurement device capable of measuring (and, if necessary, controlling) the minimum outdoor airflow rate at all expected system operating conditions within 15% of the design minimum outdoor air rate. Monitoring must be performed for at least 80% of the building’s total outdoor air intake flow serving occupied spaces. The outdoor airflow measurement device(s) must take measurements at the system level (i.e., the air-handling unit). The device must be monitored by a control system that is configured to trend outdoor airflow in intervals no longer than 15 minutes for a period of no less than 6 months. The control system must be configured to generate an alarm visible to the system operator if the minimum outdoor air rate falls more than 15% below the design minimum rate. All measurement devices must be calibrated within the manufacturer’s recommended interval.Case 2. Mechanical ventilation systems that predominantly serve densely occupied spaces1
Have a CO2 sensor or sampling location for each densely occupied space and compare it with outdoor ambient CO2 concentrations. Each sampling location must be between 3 and 6 feet above the floor. Test and calibrate CO2 sensors to have an accuracy of no less than 75 parts per million (ppm) or 5% of the reading, whichever is greater. Sensors must be tested and calibrated at least once every 5 years or per the manufacturer’s recommendation, whichever is shorter. Monitor CO2 sensors with a system configured to trend CO2 concentrations in intervals no longer than 30 minutes. The system must generate an alarm visible to the system operator and, if desired, to building occupants if the CO2 concentration in any zone rises more than 15% above that corresponding to the minimum outdoor air rate required by IEQ Prerequisite 1. CO2 sensors may be used for demand-controlled ventilation provided the control strategy complies with ASHRAE Standard 62.1-2007 ventilation rate procedure (see IEQ Prerequisite 1: Minimum Indoor Air Quality Performance, including maintaining the area-based component of the design ventilation rate).Case 3. Natural ventilation systems
Locate CO2 sensors in the breathing zone of every densely populated room and every natural ventilation zone. CO2 sensors must provide an audible or visual alarm to the occupants in the space and to the system operator if CO2 conditions are greater than 530 ppm above outdoor CO2 levels or 1,000 ppm absolute. The alarm signal must indicate that ventilation adjustments (e.g. opening windows) are required in the affected space. All monitoring devices must be calibrated within the manufacturer’s recommended interval. Permanently open areas must meet the requirements of ASHRAE 62.1-2007, Section 5.1 (with errata but without addenda2). Exemptions: If the total square footage of all space served by natural ventilation systems is less than 5% of total occupied square footage, the project is exempt from the requirements of this section. Rooms smaller than 150 square feet are also exempt.XX%
Upgrade to LEEDuser Premium to see how many projects achieved this credit. Try it free »
Got the gist of IEQc1.2 but not sure how to actually achieve it? LEEDuser gives step-by-step help. Premium members get:
- Checklists covering all the key action steps you'll need to earn the credit.
- Hot tips to give you shortcuts and avoid pitfalls.
- Cost tips to assess what a credit will actually cost, and how to make it affordable.
- Ideas for going beyond LEED with best practices.
- All checklists organized by project phase.
- On-the-fly suggestions of useful items from the Documentation Toolkit and Credit Language.
In the end, LEED is all about documentation. LEEDuser’s Documentation Toolkit, for premium members only, saves you time and helps you avoid mistakes with:
- Calculators to help assess credit compliance.
- Tracking spreadsheets for materials purchases.
- Spreadsheets and forms to give to subs and other team members.
- Guidance documents on arcane LEED issues.
- Sample templates to help guide your narratives and LEED Online submissions.
- Examples of actual submissions from certified LEED projects.