Energy and Atmosphere
Air infiltration

LEED CREDIT

Homes-v4 EAc7: Air infiltration 1-2 points

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

Case 1. Single Family
Meet the air leakage requirements shown in Table 1 or Table 2.
Case 2. Multifamily
Meet the air leakage requirements shown in Table 1 or Table 2. Meet the requirements for leakage to outside the conditioned envelope for each dwelling unit, unless the whole building can be entirely and sufficiently depressurized by a blower door(s).
Table 1. Points for reducing air leakage, in ACH50
IECC climate zone Points
1–2 3–4 5–7 8
4.25 3.5 2.75  2.0 1
3.0 2.5 2.0 1.5 2
Table 2a. Points for reducing air leakage, in cfm50 per sf envelope area
Performance requirements
IECC climate zone
Points
1–2 3–4 5–7 8
.195 .16 .125 .0925 1
.1375 .115 .0925 .0675 2
Table 2b. Points for reducing air leakage, in cmm50 per 100 square meter envelope area

Performance requirements
IECC climate zone

1–2

3–4

5–7

8

Points

5.94

4.87

3.81

2.82

1

4.19

3.50

2.82

2.06

2

ACH = Air changes per hour cfm = cubic feet per minute ELR = envelope leakage ratio IECC = International Energy Conservation Code sf = square feet cmm = cubic meters per minute
Credit only available for projects using the EA prescriptive path’
See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

Case 1. Single Family
Meet the air leakage requirements shown in Table 1 or Table 2.
Case 2. Multifamily
Meet the air leakage requirements shown in Table 1 or Table 2. Meet the requirements for leakage to outside the conditioned envelope for each dwelling unit, unless the whole building can be entirely and sufficiently depressurized by a blower door(s).
Table 1. Points for reducing air leakage, in ACH50
IECC climate zone Points
1–2 3–4 5–7 8
4.25 3.5 2.75  2.0 1
3.0 2.5 2.0 1.5 2
Table 2a. Points for reducing air leakage, in cfm50 per sf envelope area
Performance requirements
IECC climate zone
Points
1–2 3–4 5–7 8
.195 .16 .125 .0925 1
.1375 .115 .0925 .0675 2
Table 2b. Points for reducing air leakage, in cmm50 per 100 square meter envelope area

Performance requirements
IECC climate zone

1–2

3–4

5–7

8

Points

5.94

4.87

3.81

2.82

1

4.19

3.50

2.82

2.06

2

ACH = Air changes per hour cfm = cubic feet per minute ELR = envelope leakage ratio IECC = International Energy Conservation Code sf = square feet cmm = cubic meters per minute
Credit only available for projects using the EA prescriptive path’
See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Homes-v4 EAc7