Healthcare-v2009 MRc4.1: PBT source reduction - mercury in lamps 1 point

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

In addition to the credit goals outlined in MR Prerequisite 2: PBT Source Reduction—Mercury, specify and install long lasting reduced mercury fluorescent lamps consistent with the following minimum criteria:

Fluorescent Lamp Criteria
T-8 Eight-foot (Standard Output) 24,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 Eight-foot (High Output) 18,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 Four-foot (both Standard and High Output) 30,000 rated hours on instant start ballasts OR 36,000 rated
hours on program start ballasts (3 hour starts)
T-8 Two-foot and Three-foot 24,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 U-Bent 18,000 rated hours on instant start ballasts OR 24,000 rated
hours on program start ballasts (3 hour starts)
T-5 (both Standard and High Output) 25,000 rated hours on program start ballasts
Compact fluorescent lamps, non-integral ballast 12,000 rated hours
Compact florescent lamps, integral ballast, bare
bulb
10,000 rated hours
Compact fluorescent lamps, integral ballast,
covered models such as globes, reflectors & A-19s
8,000 rated hours
High Pressure Sodium Lamp Criteria
All HPS Use non cycling type or replace with LED lamps or induction
lamps
Note: Longer lamp life contributes to lower mercury use by reducing the frequency of lamp replacement.
Do not specify or install circular fluorescent lamps on the project.
Do not specify or install probe start metal halide lamps in the project.
See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

In addition to the credit goals outlined in MR Prerequisite 2: PBT Source Reduction—Mercury, specify and install long lasting reduced mercury fluorescent lamps consistent with the following minimum criteria:

Fluorescent Lamp Criteria
T-8 Eight-foot (Standard Output) 24,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 Eight-foot (High Output) 18,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 Four-foot (both Standard and High Output) 30,000 rated hours on instant start ballasts OR 36,000 rated
hours on program start ballasts (3 hour starts)
T-8 Two-foot and Three-foot 24,000 rated hours on instant start ballasts OR program start
ballasts (3 hour starts)
T-8 U-Bent 18,000 rated hours on instant start ballasts OR 24,000 rated
hours on program start ballasts (3 hour starts)
T-5 (both Standard and High Output) 25,000 rated hours on program start ballasts
Compact fluorescent lamps, non-integral ballast 12,000 rated hours
Compact florescent lamps, integral ballast, bare
bulb
10,000 rated hours
Compact fluorescent lamps, integral ballast,
covered models such as globes, reflectors & A-19s
8,000 rated hours
High Pressure Sodium Lamp Criteria
All HPS Use non cycling type or replace with LED lamps or induction
lamps
Note: Longer lamp life contributes to lower mercury use by reducing the frequency of lamp replacement.
Do not specify or install circular fluorescent lamps on the project.
Do not specify or install probe start metal halide lamps in the project.