Requirements
Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:
% Reduction | Points |
---|---|
30% | 2 |
35% | 3 |
40% | 4 |
Commercial Fixtures, Fittings, and Appliances | Current Baseline (Imperial Units) | Current Baseline (Metric units) |
---|---|---|
Commercial Toilets | 1.6 gallons per flush (gpf)* Except blow-out fixtures: 3.5 (gpf) |
6 liters per flush (lpf) Except blow-out fixtures: 13 lpf |
Commercial Urinals | 1.0 (gpf) | 4 lpf |
Commercial Lavatory (Restroom) Faucets | 2.2 gallons per minute (gpm) at 60 pounds per square inch (psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 0.5 (gpm) at 60 (psi)** all others except private applications 0.25 gallons per cycle for metering faucets |
8.5 liters per minute (lpm) at 4 bar (58 psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 2.0 lpm at 4 bar (58 psi), all others except private applications 1 liter per cycle for metering faucets |
Showerheads | 2.5 (gpm) at 80 (psi) per shower stall **** | 9.5 lpm at 5 bar (58 psi) |
For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less. |
Residential fixtures, fittings, and appliances | Current baseline (imperial units) | Current baseline (metric units) |
---|---|---|
Residential toilets | 1.6 (gpf)*** | 6 liters per flush (lpf) Except blow-out fixtures: 13 lpf |
Residential lavatory (bathroom) faucets | 2.2 (gpm) at 60 psi | 4 lpm 8.5 lpm at 4 bar (58 psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 2.0 lpm at 4 bar (58 psi), all others except private applications 1 liter per cycle for metering faucets |
Residential kitchen faucet | ||
Residential showerheads | 2.5 (gpm) at 80 (psi) per shower stall**** | flow rate ≤ 6.1 lpm (no pressure specified; no performance requirement) |
* EPAct1992 standard for toilets applies to both commercial and residential models. ** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code. *** EPAct 1992 standard for toilets applies to both commercial and residential models. **** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above. |
- Commercial Steam Cookers
- Commercial Dishwashers
- Automatic Commercial Ice Makers
- Commercial (family-sized) Clothes Washers
- Residential Clothes Washers
- Standard and Compact Residential Dishwashers
Alternative Compliance Paths (ACPs)
Europe ACP: Water Use Baseline
Projects in Europe may use the values defined by European Standards. [view:embed_resource=page_1=4887966] See all forum discussions about this credit »What does it cost?
Cost estimates for this credit
On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.
Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.
This information is also available in a full PDF download in The Cost of LEED v4 report.
Learn more about The Cost of LEED v4 »Frequently asked questions
Will the reviewers accept a spreadsheet as a plumbing fixture schedule in lieu of the plans from the Construction Documents?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
In LEED review comments I've been referred to the Water Use Reduction Additional Guidance document. I didn't know this was a required reference document.The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Should I include bar sinks? What about mop sinks or janitor sinks? Swimming pools? Safety showers? Bidets? Tub spouts? The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
We provided new showers in our project to comply with the alternative transportation credit. Should they be considered in WEp1 calculations? The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can you explain the 12-second duration for metering faucets?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can I use a nonpotable water source to contribute to WEp1 compliance?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Our project does not have any eligible water fixtures in the project boundary. Can we comply with WEp1?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
We are having trouble finding EPAct-compliant fixtures. Is that a problem?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Where can I find a clear meaning of "public" and "private" as relevant to lavatory faucets?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Our project is a factory with historically a 95% male workforce. The restroom design accounts for this. Can I argue that the male/female gender ratio is different than 50/50?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Are shower duration controls an acceptable water-saving strategy?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can I include process water savings in order to earn an Exemplary Performance point?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Addenda
Add the following to eligible fixtures section:
"For healthcare projects, fixtures used for clinical use related to medical procedures, such as surgical scrub sinks and exam rooms sinks, in hospitals and medical office buildings are excluded from the water use calculations. Medication room sinks, utility room sinks, and other exam/procedure/observation room sinks for clinical use are also excluded. Should exam/procedure/observation room sinks be used primarily for hand-washing, they may be included in the water use calculations at the project team’s discretion under the public lavatory category. If included, project teams should provide a narrative explaining the usage assumptions for these sinks.
Lavatories in hospital inpatient bathrooms and inpatient rooms are considered private. The inpatient lavatory and water closet should use the default residential usage assumptions (of five times per day per residential occupant), unless specific project conditions warrant an alternative. Lavatories in hospital inpatient rooms (outside the bathrooms) are considered private if used by patients and/or staff similarly to a residential lavatory, or can be exempt if they are used by staff primarily for medical or clinical use.
Nutrition station (pantry) sinks and hospital staff lounge sinks should be included in the water use calculations under the kitchen sink category."
The installation of bedside patient care units, which is a combined toilet and lavatory, is required for some patient rooms. Can the patient care unit be excluded from the calculations since there are no low-flow options available?
All fixtures that are covered by the EPAct 1992 must be included in the credit calculations, even if there are no low-flow options available. The use of these fixtures by only the patients in a limited area can be factored into the calculations.
Can untreated groundwater, unsuitable for drinking, contribute towards WE credits 1, 2, and 3 as a non-potable water source for irrigation and sewage conveyance?
This approach does not meet the intent of the WE credits. Although the local groundwater may not be suitable for drinking straight out of the ground, it still represents an important source of potable water. Applicable internationally.
We are seeking clarification on the use of municipally provided non-potable water for achieving WEc3 under the LEED NC version 2.2 rating system. Use of municipally supplied non-potable water meets the intent of limiting or eliminating the use of potable water and reduces the burden on municipal water supplies. However, currently, the Reference Guide does not give clear direction with concern to WEc1, WEc2 & WEc3 and municipally supplied water: WEc1 states that water savings can be claimed through the use of "water treated and conveyed by a public agency specifically for non-potable uses." WEc2 states that water savings can be claimed through the use of "municipally treated wastewater." WEc3, however, makes no statements as to whether municipally supplied recycled water can count towards water saving calculations. However, the synergies between WEc2 and WEc3 calculations leads one to conclude that municipally supplied wastewater can be used for both credit calculations. Our project will be using municipally supplied non-potable reclaimed water for both irrigation and sewage conveyance (toilet flushing). Can you please clarify whether municipally supplied reclaimed water can be used to achieve both WEc3.1 and WEc3.2?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Original ruling October 10, 2006
Municipally reclaimed water is not applicable to WEc3 achievement. This credit focuses on fixture efficiency and on-site water reuse. Applicable Internationally.
Can reverse osmosis reject water be used as an innovative wastewater source? Reverse osmosis water is often used in lab, hospital and other process water settings.
Yes, on-site reverse osmosis reject water is an acceptable non-potable water source. Applicable internationally.
For campus projects, can wastewater treatment facilities located outside of the LEED project boundary but within the campus boundary qualify as on-site for the purposes of this credit?
"Update October 20, 2016: Campus projects may continue to utilize a wastewater treatment facility located outside of the LEED project boundary as long as it is within the campus boundary for Option 2 in WEc2: Innovative Wastewater Technologies. Treated water must be infiltrated or used on-site by the project. The only change to this ruling is that the campus treated wastewater can also apply in WEc3: Water Use Reduction, if reused in the project’s flush fixtures. See the updated “Water Use Reduction Additional Guidance” document.
Original ruling April 1, 2013:
Yes, campus projects may utilize a wastewater treatment facility located outside of the LEED project boundary as long as it is within the campus boundary for Option 2. Treated water must be infiltrated or used on-site by the project.
Please note that a campus scale wastewater treatment facility located outside of the LEED project boundary would be considered a municipally supplied non-potable water source for all other Water Efficiency credits, and would not be considered an on-site non-potable water source in WEp1 Water Use Reduction. Applicable Internationally."
This is an inquiry about the calculation of the FTE in relation to our project in Zurich, Switzerland. In the LEED Reference Guide on page 53 the calculation of the FTE is based on a 8-hour working day. That means that an 8-hour occupant has an FTE value of 1.0. The standard working day in Switzerland contains 8.5 hours of work.In a FTE calculation on the basis that is provided in the LEED Reference Guide the normal working day of one single person would have the FTE value of 1.0625. As a consequence of the, in case of 1000 people fulltime staff this FTE calculation would have additional number of 63 FTE in comparion to an FTE value of 1.0.Is it possible to calculate the FTE value for this project with an 8.5 instead of 8 hour day, so that we would have the FTE value of 1.0 for a standard 8.5 hour-working day?
The project team has inquired if projects in Switzerland may use 8.5-hours as their working day instead of 8-hours as in the US. Each full-time employee based on Swiss and US labor laws works an 8.5-hour day, which includes a half-hour unpaid lunch break and two 15-minute paid breaks. In order to maintain the baseline for projects everywhere when calculating FTE occupancy, all Swiss projects, including those industries that have an overtime work culture for full-time employees, should still use the 8.0-hour work day in their FTE calculations. Applicable internationally.
Summary: Interpretation ruling pertaining to establishing the calculation baseline for Water Reduction Credits 3.1 & 3.2 when on-site tests have been conducted, and demonstrate that the supply water pressure levels (psi) to the fixtures are substantially below the 80 psi referenced within the Energy Policy Act of 1992. Context: The scope of the project incorporates new construction of four residential halls on a college campus, which house more than 250 students and staff. Three of the buildings are three stories, and the other is four stories. Description: The residence halls are incorporating a range of fixtures that are below the flow rates within the Energy Policy Act of 1992 (dual flush toilets, and faucets within the kitchens, kitchenettes, bathrooms & apartments). The showers in the residence hall are the largest water consumer (by a large %) within the residence hall buildings. To begin to understand the water amount actually used on the project, the owner conducted some initial on-site tests to determine the supply pressure to the plumbing fixtures, and how that translated into the actual flow. On-site tests for one of the buildings have been conducted on the flow rates of the shower heads with the following results: Fixture type currently installed = 2.5 gpm 1st floor: 52 psi static, 2.10 gpm 2nd floor: 46 psi static, 1.92 gpm 3rd floor: 41 psi static, 1.79 gpm 4th floor: 37 psi static, 1.85 gpm Question: o Would the design case account for the lower psi (reduced water use) by multiplying the \'Water Use\' column within the calculation template by the percentage of supply/baseline? For example for a shower on the first floor the \'Water Use" would be multiplied by 65% (52/80) or by just including 2.10 gpm as the flow rate for the fixture on this floor? o What is the appropriate methodology for establishing the calculation baseline when the water pressure supply rate (psi) is substantially lower than the 80 psi outlined as the baseline flow rates under the Energy Policy Act of 1992?
[Note: this ruling was revised on 9/1/04.] The underlying assumptions used for calculating projected water use savings should remain consistent between the baseline and design case. Supply water pressure varies across the United States and within individual buildings (as you note in your inquiry). Flow rates at 80 psi are used for the calculations in this credit for consistency and to reward use of efficient fixtures. It is recommended that all projects use the flow rates reported by the manufacturer at 80 psi for comparison with the Energy Policy Act of 1992 flow rates. If you wish to use on-site tests to report the most accurate volume of water use, you must be consistent throughout all fixtures and test both baseline and design fixtures. It is not acceptable to use flow rates at 80 psi for some fixtures and actual flow rates for other fixtures. Measurement can also be used to account for the benefits of whole-building strategies, e.g., flow restrictors at the water service entrance. Applicable Internationally.
Are swimming pools excluded from the calculations for WE Prerequisite 1?
This is correct as the prerequisite only covers fixtures specified in the Reference Guide and regulated by one of the standards listed. These fixtures and fixture fittings include water closets, urinals, lavatory faucets, showers, kitchen sink facets, and pre-rinse spray valves. Applicable internationally.
Can municipally supplied treated seawater for toilet flushing be used as a strategy for earning WEp1 and WEc1 Water Use Reduction?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Update October 1, 2013
Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
Original ruling July 1, 2012
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the pre-requisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy."
----------
10/1/13 notes: revise ruling and update resource: http://www.usgbc.org/resources/seawater-guidance
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy.
**Update October 1, 2013: Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated
Can children\'s toilets be exempt from the prerequisite because there are no low-flow options available?
There are children\'s toilets available that are 1.6 gpf. The project team must decide what is best for the clientele, but baby toilets cannot be exempt from the credit. Applicable internationally.
Can municipally supplied treated seawater for toilet flushing be used as a strategy for earning WEp1 and WEc1 Water Use Reduction?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Update October 1, 2013
Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
10/1/13 notes: link resource and edit ruling: http://www.usgbc.org/resources/seawater-guidance
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy.
**Update October 1, 2013: Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
Original ruling July 1, 2012
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy."
Does a single-occupant lockable bathroom in a commercial establishment count as "private" for flush & flow rate calculations?
The project team is requesting a ruling on whether restrooms at a commercial establishment that are only usable by one individual or family at a time are considered private or private-use facilities. The facilities that are usable by one individual or family at a time at a commercial establishment are not considered private or private-use facilities. The private or public categories for lavatory faucets are based on the UPC and IPC Standards for plumbing fixtures, and are referring to the anticipated uses and performance expectations of such faucets. Public restroom faucets are used almost exclusively for hand washing or simple rinsing, compared to lavatory faucets in homes and in other private bathrooms that are used for various purposes. Therefore the single occupancy restroom facilities at a commercial establishment are not private-use facilities and the baseline case must be calculated according to the public lavatory faucet baseline flow rate. Applicable internationally.
Can a LEED-NC project without eligible water fixtures be exempt from WEp1 Water Use Reduction?
A project without eligible water fixtures in the LEED-NC project boundary is exempt from WEp1. Should such a project wish to pursue points under WE Credit 3, they may do so by evaluating WEc3 performance based upon all of the fixtures that are necessary to meet the needs of the project occupants, even if they are located outside the project boundary.
**Update October 1, 2012: Has been made applicable to LEED for Schools v2007 and v2009.
**Update October 1, 2013: Applicable credits were updated. This ruling does not apply to Core and Shell projects.
Checklists
Step by step to LEED certification
LEEDuser’s checklists walk you through the key action steps you need to earn a credit, including how to avoid common pitfalls and save money.
Documentation toolkit
The motherlode of cheat sheets
LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.
Get the inside scoop
Our editors have written a detailed analysis of nearly every LEED credit, and LEEDuser premium members get full access. We’ll tell you whether the credit is easy to accomplish or better left alone, and we provide insider tips on how to document it successfully.
© Copyright U.S. Green Building Council, Inc. All rights reserved.
Requirements
Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:
% Reduction | Points |
---|---|
30% | 2 |
35% | 3 |
40% | 4 |
Commercial Fixtures, Fittings, and Appliances | Current Baseline (Imperial Units) | Current Baseline (Metric units) |
---|---|---|
Commercial Toilets | 1.6 gallons per flush (gpf)* Except blow-out fixtures: 3.5 (gpf) |
6 liters per flush (lpf) Except blow-out fixtures: 13 lpf |
Commercial Urinals | 1.0 (gpf) | 4 lpf |
Commercial Lavatory (Restroom) Faucets | 2.2 gallons per minute (gpm) at 60 pounds per square inch (psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 0.5 (gpm) at 60 (psi)** all others except private applications 0.25 gallons per cycle for metering faucets |
8.5 liters per minute (lpm) at 4 bar (58 psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 2.0 lpm at 4 bar (58 psi), all others except private applications 1 liter per cycle for metering faucets |
Showerheads | 2.5 (gpm) at 80 (psi) per shower stall **** | 9.5 lpm at 5 bar (58 psi) |
For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less. |
Residential fixtures, fittings, and appliances | Current baseline (imperial units) | Current baseline (metric units) |
---|---|---|
Residential toilets | 1.6 (gpf)*** | 6 liters per flush (lpf) Except blow-out fixtures: 13 lpf |
Residential lavatory (bathroom) faucets | 2.2 (gpm) at 60 psi | 4 lpm 8.5 lpm at 4 bar (58 psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 2.0 lpm at 4 bar (58 psi), all others except private applications 1 liter per cycle for metering faucets |
Residential kitchen faucet | ||
Residential showerheads | 2.5 (gpm) at 80 (psi) per shower stall**** | flow rate ≤ 6.1 lpm (no pressure specified; no performance requirement) |
* EPAct1992 standard for toilets applies to both commercial and residential models. ** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code. *** EPAct 1992 standard for toilets applies to both commercial and residential models. **** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above. |
- Commercial Steam Cookers
- Commercial Dishwashers
- Automatic Commercial Ice Makers
- Commercial (family-sized) Clothes Washers
- Residential Clothes Washers
- Standard and Compact Residential Dishwashers
Alternative Compliance Paths (ACPs)
Europe ACP: Water Use Baseline
Projects in Europe may use the values defined by European Standards. [view:embed_resource=page_1=4887966]XX%
Upgrade to LEEDuser Premium to see how many projects achieved this credit. Try it free »
Got the gist of WEc3 but not sure how to actually achieve it? LEEDuser gives step-by-step help. Premium members get:
- Checklists covering all the key action steps you'll need to earn the credit.
- Hot tips to give you shortcuts and avoid pitfalls.
- Cost tips to assess what a credit will actually cost, and how to make it affordable.
- Ideas for going beyond LEED with best practices.
- All checklists organized by project phase.
- On-the-fly suggestions of useful items from the Documentation Toolkit and Credit Language.
In the end, LEED is all about documentation. LEEDuser’s Documentation Toolkit, for premium members only, saves you time and helps you avoid mistakes with:
- Calculators to help assess credit compliance.
- Tracking spreadsheets for materials purchases.
- Spreadsheets and forms to give to subs and other team members.
- Guidance documents on arcane LEED issues.
- Sample templates to help guide your narratives and LEED Online submissions.
- Examples of actual submissions from certified LEED projects.
Will the reviewers accept a spreadsheet as a plumbing fixture schedule in lieu of the plans from the Construction Documents?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
In LEED review comments I've been referred to the Water Use Reduction Additional Guidance document. I didn't know this was a required reference document.The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Should I include bar sinks? What about mop sinks or janitor sinks? Swimming pools? Safety showers? Bidets? Tub spouts? The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
We provided new showers in our project to comply with the alternative transportation credit. Should they be considered in WEp1 calculations? The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can you explain the 12-second duration for metering faucets?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can I use a nonpotable water source to contribute to WEp1 compliance?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Our project does not have any eligible water fixtures in the project boundary. Can we comply with WEp1?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
We are having trouble finding EPAct-compliant fixtures. Is that a problem?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Where can I find a clear meaning of "public" and "private" as relevant to lavatory faucets?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Our project is a factory with historically a 95% male workforce. The restroom design accounts for this. Can I argue that the male/female gender ratio is different than 50/50?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Are shower duration controls an acceptable water-saving strategy?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Can I include process water savings in order to earn an Exemplary Performance point?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Add the following to eligible fixtures section:
"For healthcare projects, fixtures used for clinical use related to medical procedures, such as surgical scrub sinks and exam rooms sinks, in hospitals and medical office buildings are excluded from the water use calculations. Medication room sinks, utility room sinks, and other exam/procedure/observation room sinks for clinical use are also excluded. Should exam/procedure/observation room sinks be used primarily for hand-washing, they may be included in the water use calculations at the project team’s discretion under the public lavatory category. If included, project teams should provide a narrative explaining the usage assumptions for these sinks.
Lavatories in hospital inpatient bathrooms and inpatient rooms are considered private. The inpatient lavatory and water closet should use the default residential usage assumptions (of five times per day per residential occupant), unless specific project conditions warrant an alternative. Lavatories in hospital inpatient rooms (outside the bathrooms) are considered private if used by patients and/or staff similarly to a residential lavatory, or can be exempt if they are used by staff primarily for medical or clinical use.
Nutrition station (pantry) sinks and hospital staff lounge sinks should be included in the water use calculations under the kitchen sink category."
The installation of bedside patient care units, which is a combined toilet and lavatory, is required for some patient rooms. Can the patient care unit be excluded from the calculations since there are no low-flow options available?
All fixtures that are covered by the EPAct 1992 must be included in the credit calculations, even if there are no low-flow options available. The use of these fixtures by only the patients in a limited area can be factored into the calculations.
Can untreated groundwater, unsuitable for drinking, contribute towards WE credits 1, 2, and 3 as a non-potable water source for irrigation and sewage conveyance?
This approach does not meet the intent of the WE credits. Although the local groundwater may not be suitable for drinking straight out of the ground, it still represents an important source of potable water. Applicable internationally.
We are seeking clarification on the use of municipally provided non-potable water for achieving WEc3 under the LEED NC version 2.2 rating system. Use of municipally supplied non-potable water meets the intent of limiting or eliminating the use of potable water and reduces the burden on municipal water supplies. However, currently, the Reference Guide does not give clear direction with concern to WEc1, WEc2 & WEc3 and municipally supplied water: WEc1 states that water savings can be claimed through the use of "water treated and conveyed by a public agency specifically for non-potable uses." WEc2 states that water savings can be claimed through the use of "municipally treated wastewater." WEc3, however, makes no statements as to whether municipally supplied recycled water can count towards water saving calculations. However, the synergies between WEc2 and WEc3 calculations leads one to conclude that municipally supplied wastewater can be used for both credit calculations. Our project will be using municipally supplied non-potable reclaimed water for both irrigation and sewage conveyance (toilet flushing). Can you please clarify whether municipally supplied reclaimed water can be used to achieve both WEc3.1 and WEc3.2?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Original ruling October 10, 2006
Municipally reclaimed water is not applicable to WEc3 achievement. This credit focuses on fixture efficiency and on-site water reuse. Applicable Internationally.
Can reverse osmosis reject water be used as an innovative wastewater source? Reverse osmosis water is often used in lab, hospital and other process water settings.
Yes, on-site reverse osmosis reject water is an acceptable non-potable water source. Applicable internationally.
For campus projects, can wastewater treatment facilities located outside of the LEED project boundary but within the campus boundary qualify as on-site for the purposes of this credit?
"Update October 20, 2016: Campus projects may continue to utilize a wastewater treatment facility located outside of the LEED project boundary as long as it is within the campus boundary for Option 2 in WEc2: Innovative Wastewater Technologies. Treated water must be infiltrated or used on-site by the project. The only change to this ruling is that the campus treated wastewater can also apply in WEc3: Water Use Reduction, if reused in the project’s flush fixtures. See the updated “Water Use Reduction Additional Guidance” document.
Original ruling April 1, 2013:
Yes, campus projects may utilize a wastewater treatment facility located outside of the LEED project boundary as long as it is within the campus boundary for Option 2. Treated water must be infiltrated or used on-site by the project.
Please note that a campus scale wastewater treatment facility located outside of the LEED project boundary would be considered a municipally supplied non-potable water source for all other Water Efficiency credits, and would not be considered an on-site non-potable water source in WEp1 Water Use Reduction. Applicable Internationally."
This is an inquiry about the calculation of the FTE in relation to our project in Zurich, Switzerland. In the LEED Reference Guide on page 53 the calculation of the FTE is based on a 8-hour working day. That means that an 8-hour occupant has an FTE value of 1.0. The standard working day in Switzerland contains 8.5 hours of work.In a FTE calculation on the basis that is provided in the LEED Reference Guide the normal working day of one single person would have the FTE value of 1.0625. As a consequence of the, in case of 1000 people fulltime staff this FTE calculation would have additional number of 63 FTE in comparion to an FTE value of 1.0.Is it possible to calculate the FTE value for this project with an 8.5 instead of 8 hour day, so that we would have the FTE value of 1.0 for a standard 8.5 hour-working day?
The project team has inquired if projects in Switzerland may use 8.5-hours as their working day instead of 8-hours as in the US. Each full-time employee based on Swiss and US labor laws works an 8.5-hour day, which includes a half-hour unpaid lunch break and two 15-minute paid breaks. In order to maintain the baseline for projects everywhere when calculating FTE occupancy, all Swiss projects, including those industries that have an overtime work culture for full-time employees, should still use the 8.0-hour work day in their FTE calculations. Applicable internationally.
Summary: Interpretation ruling pertaining to establishing the calculation baseline for Water Reduction Credits 3.1 & 3.2 when on-site tests have been conducted, and demonstrate that the supply water pressure levels (psi) to the fixtures are substantially below the 80 psi referenced within the Energy Policy Act of 1992. Context: The scope of the project incorporates new construction of four residential halls on a college campus, which house more than 250 students and staff. Three of the buildings are three stories, and the other is four stories. Description: The residence halls are incorporating a range of fixtures that are below the flow rates within the Energy Policy Act of 1992 (dual flush toilets, and faucets within the kitchens, kitchenettes, bathrooms & apartments). The showers in the residence hall are the largest water consumer (by a large %) within the residence hall buildings. To begin to understand the water amount actually used on the project, the owner conducted some initial on-site tests to determine the supply pressure to the plumbing fixtures, and how that translated into the actual flow. On-site tests for one of the buildings have been conducted on the flow rates of the shower heads with the following results: Fixture type currently installed = 2.5 gpm 1st floor: 52 psi static, 2.10 gpm 2nd floor: 46 psi static, 1.92 gpm 3rd floor: 41 psi static, 1.79 gpm 4th floor: 37 psi static, 1.85 gpm Question: o Would the design case account for the lower psi (reduced water use) by multiplying the \'Water Use\' column within the calculation template by the percentage of supply/baseline? For example for a shower on the first floor the \'Water Use" would be multiplied by 65% (52/80) or by just including 2.10 gpm as the flow rate for the fixture on this floor? o What is the appropriate methodology for establishing the calculation baseline when the water pressure supply rate (psi) is substantially lower than the 80 psi outlined as the baseline flow rates under the Energy Policy Act of 1992?
[Note: this ruling was revised on 9/1/04.] The underlying assumptions used for calculating projected water use savings should remain consistent between the baseline and design case. Supply water pressure varies across the United States and within individual buildings (as you note in your inquiry). Flow rates at 80 psi are used for the calculations in this credit for consistency and to reward use of efficient fixtures. It is recommended that all projects use the flow rates reported by the manufacturer at 80 psi for comparison with the Energy Policy Act of 1992 flow rates. If you wish to use on-site tests to report the most accurate volume of water use, you must be consistent throughout all fixtures and test both baseline and design fixtures. It is not acceptable to use flow rates at 80 psi for some fixtures and actual flow rates for other fixtures. Measurement can also be used to account for the benefits of whole-building strategies, e.g., flow restrictors at the water service entrance. Applicable Internationally.
Are swimming pools excluded from the calculations for WE Prerequisite 1?
This is correct as the prerequisite only covers fixtures specified in the Reference Guide and regulated by one of the standards listed. These fixtures and fixture fittings include water closets, urinals, lavatory faucets, showers, kitchen sink facets, and pre-rinse spray valves. Applicable internationally.
Can municipally supplied treated seawater for toilet flushing be used as a strategy for earning WEp1 and WEc1 Water Use Reduction?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Update October 1, 2013
Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
Original ruling July 1, 2012
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the pre-requisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy."
----------
10/1/13 notes: revise ruling and update resource: http://www.usgbc.org/resources/seawater-guidance
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy.
**Update October 1, 2013: Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated
Can children\'s toilets be exempt from the prerequisite because there are no low-flow options available?
There are children\'s toilets available that are 1.6 gpf. The project team must decide what is best for the clientele, but baby toilets cannot be exempt from the credit. Applicable internationally.
Can municipally supplied treated seawater for toilet flushing be used as a strategy for earning WEp1 and WEc1 Water Use Reduction?
Update October 20, 2016: See the updated “Water Use Reduction Additional Guidance” document for new guidance on applying seawater or municipal wastewater to v2009 Water Efficiency credits.
Update October 1, 2013
Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
10/1/13 notes: link resource and edit ruling: http://www.usgbc.org/resources/seawater-guidance
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy.
**Update October 1, 2013: Note that LEED Interpretation 10117 has been updated to clarify that seawater must be treated to appropriate levels for non-potable uses in order to apply to WEc2 Innovative Wastewater Technologies; seawater that is treated to potable drinking water standards would not apply. Any on-site energy use to desalinate the seawater must be included in the EAp2/c1 calculations. Refer to the guidance document. Applicability of Seawater in Water Efficiency credits also updated.
Original ruling July 1, 2012
No, municipally supplied sources of non-potable water, including seawater, are not applicable to the WE fixture water use reduction credits, including WEp1 (D+C, EBOM) and WEc1 (CI) Water Use Reduction, or considered graywater. As stated in LI 1551 (12/12/2006) This credit focuses on fixture efficiency and on-site water reuse. In addition, the Water Use Reduction Additional Guidance document (updated 8/16/2010, http://www.usgbc.org/ShowFile.aspx?DocumentID=6493), confirms that the focus of the prerequisite is water efficiency of the installed fixtures, regardless of the water source, and only on-site water reuse is available as an alternative compliance path.
However, municipally treated wastewater (including treated seawater) applies to SSc1 - Path 9 Innovative Wastewater Technologies (CI), WEc2, Innovative Wastewater Technologies (BD+C), and can be used if the two conditions of LEED Interpretation 10117 are met: 1) the seawater is municipally supplied or explicitly approved by the municipality and 2) meets all applicable codes and permitting requirements, so as not to contaminate the municipal wastewater system with high salinity. For EBOM projects, where no wastewater credit is available, the project may apply for innovation credit for use of this strategy."
Does a single-occupant lockable bathroom in a commercial establishment count as "private" for flush & flow rate calculations?
The project team is requesting a ruling on whether restrooms at a commercial establishment that are only usable by one individual or family at a time are considered private or private-use facilities. The facilities that are usable by one individual or family at a time at a commercial establishment are not considered private or private-use facilities. The private or public categories for lavatory faucets are based on the UPC and IPC Standards for plumbing fixtures, and are referring to the anticipated uses and performance expectations of such faucets. Public restroom faucets are used almost exclusively for hand washing or simple rinsing, compared to lavatory faucets in homes and in other private bathrooms that are used for various purposes. Therefore the single occupancy restroom facilities at a commercial establishment are not private-use facilities and the baseline case must be calculated according to the public lavatory faucet baseline flow rate. Applicable internationally.
Can a LEED-NC project without eligible water fixtures be exempt from WEp1 Water Use Reduction?
A project without eligible water fixtures in the LEED-NC project boundary is exempt from WEp1. Should such a project wish to pursue points under WE Credit 3, they may do so by evaluating WEc3 performance based upon all of the fixtures that are necessary to meet the needs of the project occupants, even if they are located outside the project boundary.
**Update October 1, 2012: Has been made applicable to LEED for Schools v2007 and v2009.
**Update October 1, 2013: Applicable credits were updated. This ruling does not apply to Core and Shell projects.