Some utilities offer rebates for installing CO2 sensors in conjunction with demand-control ventilation. For example, the New York State Energy Research and Development Authority (NYSERDA) and Florida Power & Light have offered such incentives. Check w

Some utilities offer rebates for installing CO2 sensors in conjunction with demand-control ventilation. For example, the New York State Energy Research and Development Authority (NYSERDA) and Florida Power & Light have offered such incentives. Check with your local utility or DSIRE to see if rebates are available in your area (see Resources).

CO2 sensors do not provide the same benefit in non-densely occupied spaces as they do in densely occupied spaces. It is important to remember that CO2 sensors measure only CO2 generated by human occupants and they are typically not a good way to indicate

CO2 sensors do not provide the same benefit in non-densely occupied spaces as they do in densely occupied spaces. It is important to remember that CO2 sensors measure only CO2 generated by human occupants and they are typically not a good way to indicate indoor air quality in non-densely occupied spaces. CO2 monitors cannot replace outdoor air monitors and are often incorrectly preferred because they are less expensive than outdoor air delivery monitoring.

Projects without ducted make-up air must follow Option 2 for natural ventilation, and should weigh the costs and benefits of installing monitoring devices. For example, in multifamily projects and hotels where outside air is only supplied through pressuri

Projects without ducted make-up air must follow Option 2 for natural ventilation, and should weigh the costs and benefits of installing monitoring devices. For example, in multifamily projects and hotels where outside air is only supplied through pressurized hallways and operable windows. Every apartment or unit will need one CO2 sensor per unit, and many projects find this to be too costly. Mechanically ventilated common areas such as hallways and lobbies will require outdoor airflow monitors instead of CO2 sensors.

For Core and Shell projects, CO2 sensors are not required in tenant spaces that are not included in the scope of work for the LEED project. However, in order to achieve credit compliance, the base building’s mechanical system and BMS must be capable

CO2 sensors are not required in tenant spaces that are not included in the scope of work for the LEED project. However, in order to achieve credit compliance, the base building’s mechanical system and BMS must be capable of incorporating CO2 sensors into future tenant fit-outs. Including requirements for monitoring systems in tenant lease or sales agreements is recommended to help tenants earn a LEED for Commercial Interiors credit for CO2 monitors.