Insert the term "Tenant space" in alphabetical order with the accompanying text "Tenant space is the area within the LEED project boundary. For more information on what can and must be in the LEED project boundary see the Minimum Program Requirements (MPRs) and LEED 2009 MPR Supplemental Guidance. Note: tenant space is the same as project space."

ad-100000124

Replace the text with "Breathing zone is the region within an occupiedspace between 3 and 6 feet above the floor. Note that this definitionvaries from that of ASHRAE 62.1-2007, which states that the breathingzone is between 3 inches and 6 feet from the floor, and 2 feet from thewalls as well as fixed air conditioning equipment."

ad-100000150

Remove the fourth bullet item:Provide containment drains plumbed for appropriate disposal ofhazardous liquid wastes in spaces where water and chemicalconcentrate mixing occurs for maintenance or laboratory purposes.

ad-100000149

Replace the text of the third bullet with the following:In mechanically ventilated buildings, each ventilations system thatsupplies outdoor air shall comply with the following:

ad-100000148

Replace the text of the first bullet with the following:Employ permanent entryway systems at least 10 feet long in the primarydirection of travel to capture dirt and particulates entering the building atregularly used exterior entryways. Acceptable entryway systems includepermanently installed grates, grills and slotted systems that allow forcleaning underneath. Roll-out mats are acceptable only when maintainedon a weekly basis by a contracted service organization.