100002230 Getting Started Table 6 IWUR
Under the GIB section, for the Indoor Water Use Reduction credit, in the "existing features" column, revise the text to read at "Major Renovations."
Under the GIB section, for the Indoor Water Use Reduction credit, in the "existing features" column, revise the text to read at "Major Renovations."
Revise the second bullet to read as follows:
"Ensure that no more than two uses within each use type are counted for each dwelling unit."
Delete second bullet, "For the nonresidential and mixed-use setback from sidewalks requirements (c), the distance of the setback must be measured from the property line."
Further Explanation: Insert the following content as the third section in Further Explanation, between current sections "Prescriptive Path" and "Creating a Compliant 90.1 Energy Model":
"Fundamental Commissioning of Central HVAC and Service Water Heating Systems
Delete fourth bullet that reads: "Furniture is considered part of the scope if it is installed at the time of occupancy, regardless of who specified or provided it."
FSC chain of custody correction: In the first paragraph, replace with newer version of standard - Chain of Custody Standard 40-004 v3-0 instead of v2-1.
Calculating FSC Credit Contributions corrections:
Remove the following language: "(terminology in parenthesis is being phased out by may still be in use)"
Update the first 3 bullet points to read as follows:
· Products identified as FSC 100% contribute 100% FSC content.
· Products identified as FSC Mix Credit contribute 100% FSC content.
Remove the multiplier of x100 from equation 2.
EA Prerequisite Fundamental Commissioning and Verification: STEP-BY-STEP GUIDANCE:
In Step 3. Engage Commissioning Authority, replace the third bullet with the following text:
"The CxA will lead, review, and oversee the Cx process for all systems to be commissioned, including both Fundamental and Enhanced commissioning activities if Enhanced Commissioning is pursued (see Further Explanation, Systems to Be Commissioned)."
Modify the SI unit conversions:
Path 1, change 4 267 140 liters per second of outdoor air per square meter' to '4 267 140 liters of outdoor air per square meter'.
Path 2, change '1 066 260 liters per second of outdoor air per square meter' to '1 066 260 liters of outdoor air per square meter'.
Path 2, change ‘1.5 liters of outside air per second per square meter’ to ‘1.5 liters per second per square meter of outdoor air’.
Replace the text under Step 1. Determine Air-Testing Location with the following:
"Determine where in the building IAQ testing will be performed.