Use MERV 8 filtration is on any permanent mechanical system equipment used during construction. This adds to construction management tasks and could easily be overlooked and lead to loss of the credit. (This requirement appears in the LEED Online credit f

Use MERV 8 filtration on any permanent mechanical system equipment used during construction. This adds to construction management tasks and could easily be overlooked and lead to loss of the credit. (This requirement appears in the LEED Online credit form as of 10/09, even though it does not appear in the credit language or LEED Reference Guide.)

 For all spaces that may contain hazardous gas (such as garages, janitors' closets, and labs), calculate exhaust rates to confirm adequate negative pressurization. The pressurization requirements are: an exhaust rate of 0.5 CFM/SF with a pressur

For all spaces that may contain hazardous gas (such as garages, janitors' closets, and labs), calculate exhaust rates to confirm adequate negative pressurization. The pressurization requirements are: 

an exhaust rate of 0.5 CFM/SF with a pressure differential in relation to surrounding spaces of at least 5 Pascals (Pa)—.02 inches on water gauge—on average;
and when doors are closed, 1 Pa—.004 inches on water gauge—at a minimum.