Hi all-
I recieved a comment from the GBCI reviewer stating that It is not clear whether the Baseline case fan air flow rates were sized based on a 20 deg. F supply-air-to-room-air temperature difference for non-laboratory spaces and 17 deg F for laboratory spaces in the Baseline systems based on the zone heat extraction rate and supply airflow rate in the SV-A report.
- The room temperature is 75F and the AHU Supply air Temperature (75-20) 55F for the all the spaces.
- For Lab spaces, room temp= 75 and SAT= 75-17= 58F
I am unsure what else needs to happen to address the reviewer comment?