Revise the Intent to read as: "...excessive energy use and greenhouse gas emissions that disproportionately..."

Revise the second paragraph and the bullets to read as:
"ASHRAE 90.1-2016 Compliance pathways in Section 4.2.1.3 include compliance with all mandatory provisions applicable to the project scope of work, and compliance with one of the following:
 Prescriptive provisions of Sections 5 through 10
 Section 11 Energy Cost Budget Method
 Normative Appendix G Performance Rating Method. When using Appendix G, the Performance Cost Index (PCI) shall be less than or equal to the Performance Cost Index Target (PCIt) in accordance with the methodology provided in Section 4.2.1.3 (the same Building Performance Factors as are used for New Construction). Document the PCI, PCIt, and percentage improvement using metrics of cost or greenhouse gas (GHG) emissions.

Delete language under "For projects using Normative Appendix G Performance Rating Method"

Edit the bullet that starts "Exception to Manadatory Measure requirements" to read as: Exception to Mandatory Measures requirements: For ASHRAE 90.1-2016 mandatory controls provisions where the Appendix G Performance Rating Method provides a methodology for demonstrating savings between the Proposed Building Performance (PBP) and the Baseline Building Performance (BBP) projects may model the Proposed Building Performance as designed in lieu of compliance with the mandatory provisions.

Remove the word "minimum" from the last bullet of Requirements