NC-v4 EAp2:Minimum energy performance

Demand Controlled Ventilation for DOAS

We have a dedicated outdoor air system that serves a 4 story hotel. The outside air is delivered directly to the sapces via a diffuser. Would it be acceptable to use exeption b ( Multiple-zone systems without DOC of individual zones communicating with a central control panel.) to waive the DCV for meeting rooms ?

 

Thank you,

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 06/03/2021 - 14:32

This exception would only apply if the system does not have a DDC control system. The example of this given in the User's Manual is systems with pneumatic zone thermostats. 