Replace the last two sentences of the first paragraph with the following:To satisfy the requirements of this credit, the measurement device mustbe capable of measuring the minimum outdoor air intake flow with anaccuracy of plus or minus 15% when the system is providing the designminimum outdoor air rate. When the measurement device generates ameasurement of outdoor air intake flow that is more than 10% below thedesign outdoor air minimum values, the monitoring system should beconfigured to deliver a visible or audible alert to the system operator toindicate that operational adjustments may be necessary.
Credits
Date
Updated date
Campus Applicable
Off
Internationally Applicable
Off
Ref Guide Name and Edition Pre-v4
Green Interior Design and Construction, 2009 edition