Option 1, after Warehouses and Distribution Centers ONLY box, add a new box with the following:
Multifamily only
Common area entrances shall meet the requirements above. For residential units with a direct entrance to the exterior, have in place a walk off mat.
Option 2, at end add a new box with the following:
Multifamily only
Mechanical Ventilation
Establishment
Meet ASHRAE 62.2-2010 (with errata) or local equivalent, whichever is more stringent for each residential unit.
Performance
Test the flow rate of mechanical systems at least once every five years.
Cooking Appliances
Establishment
Do not have gas kitchen cooking appliances within the unit envelope.
OR
Gas fueled cooking appliances (stoves, ovens, ranges, etc.) must be hooded and mechanically vented to the outdoors.
Performance
None.
Space and Water Heating Equipment
Establishment
Gas fueled space and water heating equipment must be directly vented to the outdoors.
Performance
None.
Natural Ventilation
Establishment
Follow Chartered Institution of Building Services Engineers (CIBSE) Applications Manual AM10, March 2005, Section 4, Design Calculations, to predict sufficient airflow quantities will be achieved for effective natural ventilation.
Performance
None.