Inquiry
Please confirm that the tenant\'s scope of work does not need to include the upgrade of the existing base building HVAC equipment (that is remaining in place and not being altered) that may not meet ASHRAE 90.1 - 2007 requirements under EAp2.
Ruling
The existing HVAC does not need to be upgraded; however, all new and replacement ductwork must meet the requirements of section 6.1.1.3.4 of ASHRAE 90.1-2004. Applicable internationally.