There is a stainless steel tube veil that covers the complete building. The tubes are placed with a 1 mm spacing between each other, and the material interior cannot be seen. Therefore, we would like to conduct a test to verify if the SRI of the tubes will comply with the LEED requirements (equal or greater than 78). Due to the originality of the exterior facade, we would like to know what type of test should be conducted:
Option 1 - Test using a 4mx4m mock up of the roof assembly and test the reflectance per ASTM 1918,
Option 2 - A flat sample test of all the materials installed on the roof
Please advise if there are any other tests that would need to be conducted.

Ruling

The Referenced LEED Standard of ASTM 1918-97 has been superseded by ASTM 1918-06. For a roof with a veil design, or similar non-homogenous materials, the project should perform a SRI test to ASTM E1175 - 87(2009) Standard Test Method for Determining Solar or Photopic Reflectance, Transmittance, and Absorptance of Materials Using a Large Diameter Integrating Sphere. When submitting for LEED Certification, please include a copy of this interpretation and a summary of any testing results that document the SRI rating for the installed veil surface.Projects may wish to test any mock-up to assess credit compliance before testing installed materials, but the testing for certification should be done for the installed roofing assembly. Applicable internationally.