We propose to install (2) humidity monitors on each floor at the point where the plenum return air enters each mechanical room. Each monitor will interface with the building EMS system to provide continuous feedback on overall humidity levels. Psychometric analysis will be provided to show that in the City of Phoenix, humidification / dehumidification equipment is not needed to maintain acceptable humidity levels within the office space. Will the system and documentation described above comply with the requirements of this credit? If not, what additional information or system modification is needed?
Should the psychometric data in fact show that active humidification / dehumidification is not needed to maintain acceptable levels, the approach as described will comply with the requirements of the credit. Applicable Internationally.