Our project is subject to ASHRAE Standard 90.1-2013 for code compliance. To pursue Option 1: Energy Performance Compliance in LEED v4.1 BD+C, is there a methodology for documenting additional energy performance for LEED v4.1 projects regulated by ASHRAE Standard 90.1-2013?
Yes, projects applying Option 1: Energy Performance Compliance, and regulated by ASHRAE Standard 90.1-2013 or IECC 2015 may document achievement of LEED v4.1 BD+C EA Prerequisite Minimum Energy Performance and EA Credit Optimize Energy Performance as described below:
Comply with all mandatory provisions of ASHRAE Standard 90.1-2013 or IECC 2015.
AND
Demonstrate a Percentage improvement in the Proposed Building Performance beyond the Baseline Building performance in accordance with ANSI/ASHRAE/IESNA Standard 90.1-2013, Appendix G.
Calculate the Baseline Building Performance, Proposed Building Performance, and Percentage Improvement using metrics of cost and greenhouse gas (GHG) emissions. For each energy source serving the building, the GHG emission factors must be identical for the Baseline and Proposed building models.
The LEED prerequisite Percentage Improvement requirements may be demonstrated either using metrics of cost from Table 1 or greenhouse gas (GHG) emissions from Table 2. LEED points are calculated based on the project percent improvement for cost and GHG emissions. Total points have been divided equally between the metrics of energy cost and greenhouse gas emissions. Points are awarded according to Table 1 and Table 2.
For project percent improvement for the cost metric, on-site renewable energy may be subtracted from proposed energy cost prior to calculating proposed building performance per ASHRAE Standard 90.1-2013 Section G 2.4.1.
Table 1. Points for percentage improvement in energy performance – Cost (1-9 points NC and CS, 1-8 points Schools, 1-10 points Healthcare)
New
Construction
(except
Healthcare,
Schools,
Multifamily
Residential)
Healthcare,
Major
Renovation,
CS
Schools
Points
BD+C
(except
Schools,
Healthcare)
Points
Healthcare
Points
Schools
7%
3%
15%
Prerequisite
Prerequisite
Prerequisite
12%
5%
20%
1
1
1
17%
8%
25%
2
2
2
22%
13%
30%
3
3
3
27%
18%
35%
4
4
4
32%
23%
40%
5
5
5
37%
28%
45%
6
6
6
42%
33%
50%
7
7
7
47%
38%
-
8
8
-
52%
43%
60%
9
9
8
57%
48%
65%
EP
10
EP
-
53%
-
-
EP
-
On-site renewable energy may be subtracted from proposed greenhouse gas emissions prior to calculating proposed building performance per ASHRAE Standard 90.1-2013 Section G 2.4.1. New off-site renewable energy as defined in EA credit Renewable Energy may be subtracted from proposed greenhouse gas emissions prior to calculating proposed building performance.
Table 2. Points for percentage improvement in energy performance – Greenhouse Gas Emissions (1-9 points NC, 1-8 points Schools, 1-10 points Healthcare)
New Construction (except Healthcare, Schools, Multifamily Residential)
Healthcare, Major Renovation, CS
Schools
Points BD+C (except Schools, Healthcare)
Points Healthcare
Points Schools
7%
3%
15%
Prerequisite
Prerequisite
Prerequisite
12%
5%
20%
1
1
1
17%
8%
25%
2
2
2
23%
13%
31%
3
3
3
31%
19%
37%
4
4
4
39%
27%
43%
5
5
5
47%
35%
50%
6
6
6
55%
43%
60%
7
7
7
65%
50%
-
8
8
-
80%
65%
80%
9
9
8
100%
80%
100%
EP
10
EP
-
100%
-
-
EP
-