We have a C&S project - combination of office and lab. Appendix G requires an exception for labs, however, due to the C&S project type we are currently not modeling any zones outside of the base building common spaces & perimeter / core zones within the tenant spaces. Does the Appendix G lab exhaust system exception (based on exhaust cfm) still apply to C&S models?
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5907 thumbs up
October 14, 2020 - 9:35 am
Yes. You will still need to model the whole building. If you know that the building is a combination of office and lab than some of the tenant spaces should be modeled as lab using the exception to G3.1.1.