I was wondering if I could pick someone's brains regarding the unmet hours test when running an energy model for ASHRAE 90.1 App. G compliance.

So far we have been sticking to the 2°F temperature difference, both for heating and cooling setpoints; however, would it be possible to go higher than that? Is there actually a limit we need to adhere to?

Thank you.

Kind regards,

Nikos 

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 07/28/2020 - 17:53

I don't think there are any specific space temperature setting requirements in 90.1.

Mon, 08/03/2020 - 08:44

Thanks very much for the reply Marcus. So am I right to be thinking that we would be allowed to set the tolerance as high as we wish and have no unmet load hours in our models? Nikos

Mon, 08/03/2020 - 13:04

Let me make sure I understand. Expalin the temperature difference you mentioned. Is it the dead band? That should be at least 5 degrees F (Section 6.4.3.1.2). Your temperature settings in the proposed model should reflect the temperature setting expected to be used in the building. The baseline should use the same settings.