NC-v4 EAp2:Minimum energy performance

Data Centre energy model baseline

Hello,

For a large data centre, I was thinking the baseline should be:

- HVAC: system 8

- CRAC fan power: Ls x 0.0021 + A as per ASHRAE table G3.1.2.9

Is this correct?

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 01/23/2019 - 16:20

Sounds right. Table G3.1.2.9 is a part of Section G3.1.2.10 which is how you calculate baseline fan power.

Mon, 03/11/2019 - 09:07

Thank you Marcus. 1) What about table 6.8.1K? Do I need to use this table, e.g., air conditioner water cooled, for the baseline CRAC fan power? It appears that the actual CRAC equipment SCOP is around 20, much better than 2.40. 2) For baseline chiller, table 6.8.1c mentions only full load and IPLV COP, how do I define the COP at part load conditions? I.e., a typical chiller performance chart gives COP at 100%, 90%, 80%...until 20% part load, how do I decide the baseline COP at all these part load conditions?

Wed, 03/13/2019 - 10:25

Ameet, for the SCOP you are comparing values in IP and SI units most likely. The ASHRAE table gives the SCOP in SI units, that's why the difference is huge. The maximum theoretical (Carnot Cycle) COP value is 8.8 in SI units.

Mon, 03/18/2019 - 19:24

1. You will not use that table for the baseline system. 2. You would use a default chiller curve and autosize the system. You generally do not decide the COP at part load conditions. You enter a full load COP and a curve.