NC-v4 EAp2:Minimum energy performance

Baseline systems modeling requirements

Hello!

I'm having some doubts regarding how to model the baseline (BB) building.

When modelling a baseline system (system #5 - VAV):

 

1) -

In order to determine if a BB HVAC system needs exhaust energy recovery using ASHRAE 90.1 - 2010 table 6.5.6.1, do the % of OA and supply airflow rate refer to that baseline system or do they refer to the corresponding Proposed Design (PD) HVAC system (modeling the same spaces)?

 

2 -

In the BB building, for a space that has more than 50 m2 and ocupancy greater than 40 people per 100 m2 and that is served by system #5 (VAV) with Exhaust energy recovery complying with section 6.5.6.1. As per ASHRAE 90.1 - 2010, section 6.4.3.9 (Demand Control Ventilation), does the space needs to be modeled with demand control ventilation or is it exempted by exception a)?

Hope I made myself clear.

Thank you al in advance!

1

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Mon, 10/29/2018 - 15:30

1. To the baseline system. 2. Exempted by a.

Add new comment