NC-v4 EAp2:Minimum energy performance

Baseline case system selection- Exception

Hi All,

We are working in a pharmaceutical industry project which has a conditioned area of 78000sq.ft; as per ASHRAE 90.1 2010 the baseline case system is System 6 – Packaged VAV with PFP Boxes.

Since it is pharmaceutical industry we have a zones having special pressurization relationships, cross contamination requirements and code required circulation rates. So can we use System 4- PSZ-HP?

Whether this type of exception is possible in ASHRAE 90.1 2010 G3.1.1 Baseline HVAC system type and description.

Thanks in Advance

 

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 06/20/2018 - 13:35

Yes, you have to use System 4- PSZ-HP.

Wed, 06/20/2018 - 13:46

Check out the exceptions under G3.1.1. You must use the ones that apply to your project.

Thu, 06/21/2018 - 16:09

If the project was v2009, it would be pretty cut and dry.  In 90.1-2010 the exception for spaces with code-required air change rates or special pressurization requirements has been removed.  The only way you can use Sys4 rather than Sys6 is if G3.1.1 exception b applies, which is for spaces with loads that differ by more the 10 Btu/h/ft2 or schedules that differ by more than 40 equivalent full load  hours per week.