I am modelling a CI offices that are in a CS certified buulding, in order to select the HVAC system type for the baseline, it is stated in the guide that this must be based on the building´s area and number of floors (not the project´s area and number of floors) the system correspond to a System 8 VAV with parallel fan powered boxes and reheat. However, there is nothing in the guide regarding the type and number of chillers, it should be based also in the cooling capacity of the whole building or only in the cooling capacity of the project?
Thanks in advance
Kind regards
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5909 thumbs up
October 9, 2017 - 6:24 pm
The system selection is based on the entire building so the number of chillers in the central plant should also be based on the entire building load.