FAQs about EAp2 :

Can the Passive House Planning Package (PHPP) be used to energy model for LEED?

Is it acceptable to model a split-type AC with inverter technology compressor as a heat pump, like modeling VRF?

Can the Trace 700 'LEED Energy Performance Summary Report' by uploaded to LEED Online in lieu of the Section 1.4 tables spreadsheet?

A portion of our building envelope is historic. Can we exclude it from our model?

Which baseline HVAC system do I use if my building has no heating or air conditioning?

For an existing building, do I need to rotate the model?

Our project has a diesel backup generator. Should we include it in our energy model?

Our project has a large process load—75%. Despite our efforts to make an efficient HVAC design, the cost savings are minimal. What can we do to earn this prerequisite and be eligible for LEED certification? Is there any flexibility in how we model the p

Can SHGC be higher in the proposed than in the baseline model?

Our process load is higher than 25%. Do we have to justify that?

Do I need to justify the electrical and fuel rates I am using in my model?

Our local code references ASHRAE 90.1-2010. Should I use that for my documentation, or 90.1-2007?

Can I claim exterior lighting savings for canopy lighting even though a baseline model cannot include shading elements?

The project is built on a site with existing exterior lighting installed. How should this be accounted for?

Can mezzanines open to floors below be excluded from the energy model?

How do I provide a zip code for an international location?

For a project outside the U.S., how do I determine the climate zone?

For a project outside the U.S., how do I determine the Target Finder score?

Do hotel rooms need automatic light shut-off control?

How commonly are the 90.1 mandatory compliance forms submitted as part of EAp2/EAc1?

View answers »

Forum discussion

NC-2009 EAp2:Minimum Energy Performance

LPD of Building Area Method

1. If we decides to use 'Building area method' for energy modeling. We have to building area type including office and parking garage. Office baseline model LPD is 1 W/sf and parking garage is 0.3 W/sf. Let's say the office area is 10,000 sqft and parking is 5,000. This gives the total watt 10,000 W + 1,500 W = 11,500 W. Total LPD is 11500/15000 = 0.77 W/sf. Should we model 0.77 W/sf for both parking and office or should we model 1 W/sf for office and 0.3 W/sf. Our project reviewer seems to prefer the 0.77 W/sf approach but we just want to make sure. 2. For the proposed model, we can use the building area method, right? For example, if the building has total lighting watt of 7500 W and the area is 15000 sf. LPD is 0.5 W/sf. Can will use this average LPD in all zones? Thanks Thanks

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 08/18/2016 - 15:25

1. I would model 1 W/sf for office and 0.3 W/sf for Parking. Total LPD is for compliance with prescriptive power allowance not for modelling. 2. If you choose Building Area Method, you must use Building area method with the same Building criteria selection for proposed and Baseline and for proposed. So the answer is,Yes, model same LPD all parking, and same LPD in all office zones. That said, in my experience Space by space always gives greater savings than Building Area Method. If you have the option go for that. Best.

Thu, 08/18/2016 - 14:46

Thank Santiago. What do you think Marcus?

Thu, 08/18/2016 - 14:47

Thank Santiago. What do you think Marcus?

Fri, 08/19/2016 - 15:51

1. Modeling the two spaces with different LPDs is certainly more accurate. If you use 0.77 in all spaces you are shifting internal loads from conditioned to unconditioned spaces. Technically the reviewer is correct but sometimes the rules make no sense and should be slightly bent. This may or may not be a conservative approach. If it is conservative you could try to make that case. 2. You should use the same methodology in both the baseline and proposed models. I agree that the savings is often greater using the space-by-space method. It is also the more accurate way to model most buildings.

Fri, 08/19/2016 - 16:06

Thanks Marcus I found the clear instruction in Advanced Energy Model Guide from USGBC. it clearly said that we have to input LPD of each building area type. We plan to use to response to the reviewer.

Fri, 08/19/2016 - 16:07

Thanks Marcus I found the clear instruction in Advanced Energy Model Guide from USGBC. it clearly said that we have to input LPD of each building area type. We plan to use to response to the reviewer.

Fri, 08/19/2016 - 16:29

Good to know the right way aligns with the guidelines!

Thu, 06/15/2023 - 05:07

Dear Marcus,   If we take a building area method, LPD will same value in all area. However, I'm concered that each rooms internal lighting load.  

Thu, 06/15/2023 - 12:21

It doesn't matter. It only matters if you are trying to "design" the baseline system. It is not designed in the same way as the proposed systems, so again it doesn't matter. Engineers seem to often fall into trying to design the baseline system but it doesn't have to actually operate in reality. That said I think it is far more accurate to use the Space-by-Space Method so if you remain concerned, use that one.

Thu, 06/15/2023 - 12:35