CI-v4 EAp2:Minimum energy performance

Daylight controls

Dear all, We are working on a project to be certified CI v4. The use is a software development office, the building is 100% glazing in a very hot climate. The owner will be installing blinds due to the glare factor and visual comfort for employees. The blinds are to be down during occupancy hours, especially in the south facade. Is there any way that we could be exempt from the daylight control requirements? It seems that the investment in the daylight control would not be fruitful in this situation.

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Mon, 07/18/2016 - 18:04

Gabriela I am assuming the blinds are not "black out" type. They are probably for glare control, as such, they are probably translucent. Again, these are assumptions. Though ASHRAE 90.1-2010 Mandatory Requirements are for Daylighting Controls according to the "PRIMARY SIDE LIT AREA" definitions and Figure 3.3. The only exceptions are: if the adjacent building is twice as high as the distance to the windows (i.e. a tall building next to your project, on that facade only); if your effective aperture is less than 0.10; Retail spaces Check the assumptions I made, but even black out drapes are not included in the exemptions, unfortunately your project may have inherited a bad envelope design from the Base Building. Thanks Jorge

Mon, 07/18/2016 - 18:46

Thank you Jorge! The blinds are not black out, they only let 1% of light through, as far as we know from the owner. I've looked at the reference you mention, and it seems there is no way around the requirement for this case. Thanks for your help!

Add new comment

To post a comment, you need to register for a LEEDuser Basic membership (free) or login to your existing profile.